Up: Sediver

Sediver Catalog 1970 105 of 136
|
|
| |
Toughened glass insulator
| F 12 P |
 |
| Spacing |
Dimension P |
mm |
130 |
140 |
146 |
| Power frequency withstand voltage: |
|
dry one minute |
kV |
70 |
|
wet one minute |
kV |
40 |
| Dry impulse withstand voltage: |
|
positive |
kV |
125 |
|
negative |
kV |
110 |
| Minimum puncture voltage |
kV |
130 |
| Minimum electro-mechanical failing load |
kg |
12.000 |
|
|
| Creepage distance |
mm |
370 |
|
|
| Approx. nett weight |
kg |
4,700 |
| Export packing: in crates of 6 units |
| |
Volume |
m³ |
0,077 |
| |
Gross weight |
kg |
32 |
Tests: in accordance with I.E.C. Publication No. 274-1968
The dimensions of the metal fittings comply fully with I.E.C
Publication 120, 16 mm A size. |
|
|